Static Excitation Controller
Technical Specifications
|
SENSING voltage at U,V or SENS
|
225 - 475 VAC 2 phase.
|
|
FEEDING VOLTAGE. ( If provided )
|
260VAC. Max.
|
|
FREQUENCY.
|
50/60 Hz.
|
|
OUTPUT. AT
F+,F- or FIELD
|
DC Voltage.
|
100.@ 415 VAC at U,V or 40% of feeding voltage.
|
|
Current.
|
6.0 A, continuous and 10.0 Amp. Intermittent for 10 sec.
|
|
Resistance
|
15 ohms min.
|
|
REGULATION.
|
+/- 1.0 %.
|
|
AVR RESPONSE.
|
20 ms.
|
|
UNDER Frq. PROTECTION.
|
45 - 60 Hz. settable, Slop - 12 volts/Hz.
|
|
RESIDUAL VOLTAGE.
|
5 Volts, min @ AVR terminals at U,N or feeding.
|
|
OPERATING TEMPERATURE.
|
-40 to + 70 Degree C
|
|
PROTECTION FUSE.
|
6.0 A, quick acting (19mm X 5mm glass cartridge)
|
Controls
|
V - Set.
|
To adjust generator output voltage.
|
Clockwise increases output voltage.
|
|
Stab.
|
To prevent voltage hunting.
|
Clockwise increases damping effect.
|
|
U/F set.
|
To set UFRO knee point.
|
Clockwise increases knee point setting.
|
|
OL set.
|
To set over excitation tripping.
|
Clockwise increases excitation tripping voltage.
|
Physical Dimension/Weight
|
L x W x H
|
100mm X 100mm X 35mm
|
|
Weight.
|
370 gms.
|
|
MOUNTING.
|
6.6mm X 2 holes, at center distance of 153.0mm.
|
Important
- The discrete power component TYN 1225/612 and diode 20ETS12 can be replaced if failed.
Caution
- Isolate AVR while flashing or insulation testing of the Alternator.
- Installation and adjustment must be carried-out by skilled technician only.
- O/L tripping is the optional facility and would be available on request.
|